Deficiency description
System: 07 - Fire Safety
sub-system: N/a - No Subsystem
cause:
description Of Deficiency: Doors And Door Frames In "b" Class Divisions And Means Of Securing Them Shall Provide A Method Of Closure Which Shall Have Resistance To Fire Equivalent To That Of The D Ivisions. Fire Doors 11-2-004 Did Not Close Properly. 74 Solas 20 11-2/9.4.1.2.1 (16ac)
due Date: 12/12/2023 12:00:00 Am
deficiency Resolved? Yes
resolved Date: 12/11/2023 12:00:00 Am
resolution Description: Class Report Attesting To Adjustment And Validation Of Proper Operation Per Solas Provided And Attached To This Activity.
system: 07 - Fire Safety
sub-system: N/a - No Subsystem
cause:
description Of Deficiency: Escape Doors From Public Spaces That Are Normally Latched Shall Be Fitted With A Means Of Quick Release. Such Means Shall Consist Of A Door-latching Mechanism Incorporating A Device That Releases The Latch Upon The Application Of A Force In The Direction Of Escape Flow. Twist Locks That Were Not Integrated Into The Release Latch Were Observed In Escape Routes In The Following Areas: Entourage Lounge Leading To Arcade, The Humidor, And The Ice Bar. 74 Solas 20 I-2/13.3.2.6.2 (10c)
due Date: N/a
deficiency Resolved? Yes
resolved Date: 12/11/2023 12:00:00 Am
resolution Description: Class Report Attesting To Adjustment And Validation Of Proper Operation Per Solas Provided And Attached To This Activity.
system: 07 - Fire Safety
sub-system: N/a - No Subsystem
cause:
description Of Deficiency: Fire Doors In Main Vertical Zone Bulkheads, Galley Boundaries And Stairway Enclosures, The Approximate Time Of Closure For Hinged Fire Doors Shall Be No More Than 40 S And No Less Than 10 S From The Beginning Of Their Movement. Fire Doors 13-5-004, 13-4-008, 13-3-008, 13-2-005, 13-1-003, 11-2-006, 11-1-002, 10-1-004, 10-3-003, 10-3-002, 10-3-009 Closed In Less Than 10 Seconds. 74 Solas 20 11-2/9.4.1.1.5.2 (16ac)
due Date: 12/12/2023 12:00:00 Am
deficiency Resolved? Yes
resolved Date: 12/11/2023 12:00:00 Am
resolution Description: Class Report Attesting To Adjustment And Validation Of Proper Operation Per Solas Provided And Attached To This Activity.
system: 11 - Life Saving Appliances
sub-system: N/a - No Subsystem
cause:
description Of Deficiency: Lifejackets Shall Be So Placed As To Be Readily Accessible And Their Positions Shall Be Plainly Indicated. Assessible Cabin (ada) Lifejacket Location Is Marked On Lower Level Of Closet And Underneath The Bed, But The Lifejackets Were Stored Only Under The Bed. 74 Solas 20 111/7.2.2 (16ac)
due Date: 12/12/2023 12:00:00 Am
deficiency Resolved? Yes
resolved Date: 12/11/2023 12:00:00 Am
resolution Description: Class Report Attesting To Corrective Action Provided And Attached To This Activity.
system: 07 - Fire Safety
sub-system: N/a - No Subsystem
cause:
description Of Deficiency: The Construction Of Doors And Door Frames In 'a" Class Divisions, With The Means Of Securing Them When Closed, Shall Provide Resistance To Fire As Well As To The Passage Of Smoke And Flame Equivalent To That Of The Bulkheads In Which The Doors Are Situated. Fire Doors 13-5-004, 13-3-003, 13-3-002, 11-1-002, 10-5-005 Did Not Close Properly. 74 Solas 20 11-2/9.4.1.1.2 (16ac)
due Date: 12/12/2023 12:00:00 Am
deficiency Resolved? Yes
resolved Date: 12/11/2023 12:00:00 Am
resolution Description: Class Report Attesting To Adjustment And Validation Of Proper Operation Per Solas Provided And Attached To This Activity.
system: 07 - Fire Safety
sub-system: N/a - No Subsystem
cause:
description Of Deficiency: The Means Of Escape, Including Stairways And Exits, Shall Be Marked ... The Marking Must Enable Passengers To Identify The Routes Of Escape And Readily Identify The Escape Exits. The Route Of Escape Signs For Crew Egress Near B-04-04-007 And B-04-05-040 Lead Back Into Crew Areas Instead Of A Stairway, Cooridor Or Open Deck Space. Route Of Escape Sign Near Door 6-4-16 Leads To A Locked Door. Route Of Escape Is Not Indicated On The Fire Control Plan. 74 Solas 20 Ii-2/13.3.2.5.1 (16ac)
due Date: 12/12/2023 12:00:00 Am
deficiency Resolved? Yes
resolved Date: 12/11/2023 12:00:00 Am
resolution Description: Class Report Attesting To Removal Of Sign In Question Provided And Attached To This Activity.